Products
Input ±50 - ±200A, Output ±4V, Power Supply ±15V, Aperture 12x10mm.
The TKC-PT3 series current sensor is an open loop device provides accurate electronic measurement of DC, AC or pulsed currents. This series current sensor has rated current input between 50A and 200A, meansure range upto 600A, with wire, no potentiometer. It has 1% accuracy, very small size, very reliable. Available for appearance customization.
Technology :
Open loop Hall effectMax. Nominal Value :
±200AMax. Measuring Range :
±600AOutput Signal :
±4VSupply Voltage :
±15 ±5%Accuracy :
1%Op. Temperature :
-40 °C / 105 °CMounting :
Aperture 12x10mmWeight :
99gMOQ :
100
Electrical data (RL=10kΩ,CL=10000PF) |
Type Parameter |
TKC50PT3 |
TKC100PT3 |
TKC150PT3 |
TKC200PT3 |
Unit |
Rated input current |
±50 |
±100 |
±150 |
±200 |
A |
Measure current range |
±150 |
±300 |
±450 |
±600 |
A |
Rated output voltage |
±4±1.5% |
V |
|||
Supply voltage |
±15±5% |
V |
|||
Consumption current |
≤60 |
mA |
|||
Offset voltage |
@Ta=25℃、铁芯消磁后 ≤±50 |
mV |
|||
Hysteresis |
@ If=0~1×IP ≤±150 |
mV |
|||
Offset voltage drift |
@ Ta= -10~+80℃ ≤±2.0 |
mV/℃ |
|||
Amplitude voltage drift |
@ Ta=-10~+80℃ 0.08 |
%/℃ |
|||
Linearity |
@ If=IP ≤1.0 |
%FS |
|||
Response time |
@ di/dt=100A/μS或IPN/μs的较小一方 ≤10 |
μS |
|||
Bandwidth |
@-3dB DC±25 |
KHz |
|||
Galvanic isolation |
@ 50HZ/60HZ,AC,1min 2.5(导体通孔-端子一括间) |
KV |
|||
Isolation resistance |
@ DC 500V 500(导体通孔-端子一括间) |
MΩ |
*Product updates, iterations, and parameter changes will not be notified separately
Applications |
Variable speed drives
Welding machine
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Electrochemical
Mechanical dimension(for reference only) |
Remarks:
1. All dimensions are in mm.
2. General tolerance ±1mm
Directions for use |
1. It will be in a forward direction when the Ip flows according to the direction of the arrowhead.
2. The primary conductor should be≤120℃.
3.The dynamic performance (di/dt and the response time) is the best when the primary hole is fully filled with the bus bar.
4. When the current will be measured goes through a sensor, the voltage will be measured at the output end.
(Note: The false wiring may result in the damage of the sensor)
5. Customs can adjust Output amplitude of the sensor by needs.
6. Custom design in the different rated input current and the output voltage are available.
Further Note |
L/T: Large quantity in 14 days
customized: Support OEM/ODM, Laser marking, Packing
Warranty: 2.5 years
After-sale service: within 24 hours
Packing and Shipment |
Add: NO.80 Feitian Avenue, Lukou Street, Jiangning District, Nanjing City
Copyright @2023 Nanjing Token Electronics Science&Technology Co., Ltd. All Rights Reserved. Sitemap | Blog | Xml | Privacy Policy Network Supported