Products
Input ±500 - ±5000A, Output ±4V, Power Supply ±15V, Aperture 64x21mm.
The TKC-HAX series current sensor is an open loop device provides accurate electronic measurement of DC, AC or pulsed currents. This series current sensor has rated current input between 500A and 5000A, meansure range upto 10000A, with wire, no potentiometer. It has 1% accuracy, very small size, very reliable. Available for appearance customization.
Technology :
Open loop Hall effectMax. Nominal Value :
±5000AMax. Measuring Range :
±10000Output Signal :
±1VSupply Voltage :
±15 ±5%Accuracy :
1%Op. Temperature :
-40 °C / 105 °CMounting :
Aperture 64x21mmWeight :
520gMOQ :
100
Electrical data (Ta=25℃±5℃,RL=2KΩ,CL=10000PF) |
Type Parameter |
TKC 500HAX |
TKC 600HAX |
TKC 800HAX |
TKC 1000HAX |
TKC 1500HAX |
TKC 2500HAX |
TKC 3000HAX |
TKC 5000HAX |
Unit |
Rated input (Ipn) |
±500 |
±600 |
±800 |
±1000 |
±1500 |
±2500 |
±3000 |
±5000 |
A |
Measure range(Ip) |
±1500 |
±1800 |
±2400 |
±3000 |
±4500 |
±5000 |
±6000 |
±10000 |
A |
Ratedoutputvoltage |
@Ip=±Ipn ±4±1% |
V |
|||||||
Supply voltage |
±15 ±5% |
V |
|||||||
PowerConsumption |
+28,-15 |
mA |
|||||||
Offset voltage |
@Ip=0 ±20 |
mV |
|||||||
Magnetic offset |
@Ip=±Ipn-0 ±10 |
mV |
|||||||
Offset drift |
@ -40~+85℃ ≤±0.5
|
mV/℃ |
|||||||
Output drift |
@ -40~+85℃ ≤±0.5 |
mV/℃ |
|||||||
Linearity |
@Ip=0-±Ipn ≤±1 |
%FS |
|||||||
Accuracy |
@ IPN ,Ta=25℃(excluding offset) ≤±1 |
%FS |
|||||||
Response time |
@50A/μS, 10%-90% ≤5 |
μS |
|||||||
Bandwidth |
@-3dB DC±25 |
KHz |
|||||||
Galvanic isolation |
@ 50HZ/60HZ,AC,1min 5 |
KV |
|||||||
Isolation resistance |
@ DC 500V 1000 |
MΩ |
*Product updates, iterations, and parameter changes will not be notified separately
Applications |
Variable speed drives
Welding machine
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Electrochemical
Mechanical dimension(for reference only) |
Remarks:
1. All dimensions are in mm.
2. General tolerance ±1mm.
Directions for use |
1. When the current will be measured goes through a sensor, the voltage will be measured at the output end.
(Note: The false wiring may result in the damage of the sensor).
2. Customs can adjust Output amplitude of the sensor by needs.
3. Custom design in the different rated input current and the output voltage available .
Further Note |
L/T: Large quantity in 14 days
customized: Support OEM/ODM, Laser marking, Packing
Warranty: 2.5 years
After-sale service: within 24 hours
Packing and Shipment |
Add: NO.80 Feitian Avenue, Lukou Street, Jiangning District, Nanjing City